Thermal power | 200 | kW |
Adapted to work with the burner | ZST-180 | |
The thermal power of the burner ZST | 200 | kW |
The fuel used | Sawdust and wood chips up to 30 mm, moisture content of 30-50% | |
Thermal power regulation | 30 – 100 | % |
Of boiler a heated surface | 18 | m2 |
Permissible static pressure | 0,25 | MPa |
Outgoing water temperature max. | 95 | °C |
Required thrust for the boiler | >2,0 | Pa |
Recommended temperature of the smoke | 180 – 200 | °C |
Thermal efficiency factor by using ZST | >=78.7 | % |
Boiler weight with isolation | 2000 | kg |
Of water a requirement | l | |
Length | 1500 | mm |
Height | 1950 | mm |
Width | 1200 | mm |
The output of the the chimney | 350 x 350 | mm |
Of tubes diameter | DN 65 | mm |